A-Z Manufacturers (HAG - The Door Specialists ) |  CAWS Index

View larger image of HAG Fire Curtain HFS Plus from HAG - The Door Specialists Fire Curtain HFS Plus HAG

A fire protection curtain which provides the best levels of protections for fire and irradiance to property and personnel. It is designed to provide safe passage next to the curtain (for corridor and escape routes) and protection for close contact. Complete with smoke seals as standard to provide 120 minutes of smoke protection. Standards: Fire integrity – E: 120 minutes.Irradiance – W: 120 minutes.Insulating Zone – IZ: 120 minutes (measured from 50 mm from face of specimen).When tested to EN 1634-1. Classifications as EN 13501-2:2007+ A1: 2009, E240 EW60, BS EN 1634-1:2008, BS EN 1363-1:1999, BS EN 1363-2:1999, BS EN 949, EN1634-3, BS EN 12101 Annex B, EN 13501-2:2007+ A1:2009 and PAS 121.Applications:Suitable for use in airports, hospitals, kitchen servery hatches, offices, retail units and schools.Box:The fire curtain assembly comprises a box housing which includes the motorized barrel and wrapped curtain. The box is attached to channel section guides at each end – these guides are the main fixing point for the entire system. Curtain:The curtain is manufactured from a woven fibreglass and stainless steel fabric; in many cases this is coated with intumescent silicone.Guide rails:100 x 50 mm galvanized steel.Head box:Galvanized steel: Up to 4 m high: 210 x 240 mm. Bottom rail:Industry-standard ‘bell’ formed from galvanized steel.Operation:Single phase electric through 24 VDC motor.Controls:Supplied with gravity failsafe control panel with inbuilt lead-acid battery support.Finish:Head box, guides and bottom rail are galvanized and can be powder coated as required to any standard RAL or BS 4800 colour. Curtains are silver grey or charcoal finish, dependent on specification.Fixing:Face or reveal fixing to steel, masonry, hardwood or fire-boarded softwood.Safety vision panels:Size: 270 x 400 mm.Certified to two hours' fire protection.

A fire protection curtain which provides the best levels of protections for fire and irradiance to property and personnel. It is designed to provide safe passage next to the curtain (for corridor and escape routes) and protection for close contact. Complete with smoke seals as standard to provide 120 minutes of smoke protection.

Standards:

  • Fire integrity – E: 120 minutes.
  • Irradiance – W: 120 minutes.
  • Insulating Zone – IZ: 120 minutes (measured from 50 mm from face of specimen).

When tested to EN 1634-1. Classifications as EN 13501-2:2007+ A1: 2009, E240 EW60, BS EN 1634-1:2008, BS EN 1363-1:1999, BS EN 1363-2:1999, BS EN 949, EN1634-3, BS EN 12101 Annex B, EN 13501-2:2007+ A1:2009 and PAS 121.

Applications:

Suitable for use in airports, hospitals, kitchen servery hatches, offices, retail units and schools.

More about Fire Curtain HFS Plus HAG:
As standard - Options

Fire Curtain HFS Plus HAG
 Manufacturer:
HAG - The Door Specialists .
  -Web:www.hag.co.uk.
  -Tel:+44 (0)800 072 3444.
  -Product reference:
HAG Fire Curtain HFS Plus.
 Finish:
[Galvanized]. - Standard.
[Galvanized and powder coated]. - Optional; insert RAL or BS 4800 colour requirement.
 Controls:
[None].
[Audio/ visual warning devices].
[Beam sensor].
[Delayed drop programme].
[Emergency retract switch].
[Split drop programme].
 Fixing:
[Face].
[Reveal].
 Safety vision panels:
  -Spot height 500 mm:
[Not required].
[Required]. - Insert quantity; consult manufacturer for details.
  -Spot height 1500 mm:
[Not required].
[Required]. - Insert quantity; consult manufacturer for details.


top ^

Guidance

for Fire Curtain HFS Plus HAG

from HAG - The Door Specialists

More about Fire Curtain HFS Plus HAG: As standard - Options

As standard

Box:

The fire curtain assembly comprises a box housing which includes the motorized barrel and wrapped curtain. The box is attached to channel section guides at each end – these guides are the main fixing point for the entire system.

Curtain:

The curtain is manufactured from a woven fibreglass and stainless steel fabric; in many cases this is coated with intumescent silicone.

Guide rails:

100 x 50 mm galvanized steel.

Head box:

Galvanized steel: Up to 4 m high: 210 x 240 mm.

Bottom rail:

Industry-standard ‘bell’ formed from galvanized steel.

Operation:

Single phase electric through 24 VDC motor.

Controls:

Supplied with gravity failsafe control panel with inbuilt lead-acid battery support.

Options

Finish:

Head box, guides and bottom rail are galvanized and can be powder coated as required to any standard RAL or BS 4800 colour. Curtains are silver grey or charcoal finish, dependent on specification.

Fixing:

Face or reveal fixing to steel, masonry, hardwood or fire-boarded softwood.

Safety vision panels:

  • Size: 270 x 400 mm.
  • Certified to two hours' fire protection.

Further Information

Literature:

RIBA Product Selector

Additional information may be available for HAG - The Door Specialists from ribaproductselector.com.

Contacts:

www.hag.co.uk

info@hag.co.uk

T: +44 (0)800 072 3444

F: +44 (0)117 965 7773