A-Z Manufacturers (Gilgen Door Systems UK Ltd) |  CAWS Index

View larger image of Firetex 60 Tubular Motor from Gilgen Door Systems UK LtdFiretex 60 Tubular Motor

A power operated steel single-skinned fire resistant automatic vertical shutter consisting of concave, solid profiles. Offers good security and fire resistance with a lighter duty material construction than the larger Firetex 240 model and the additional benefit of a concealed electric motor drive system Fire performance to DIN 4102: Door section element materials are Class A2 (non-flammable) and have been tested and assessed to provide maximum 1 hour resistance in accordance with BS 476-22. Gilgen commercial duty, electrically operated steel fire resistant vertical rolling shutter doors are designed for small apertures in industrial and commercial applications and are suitable for automatic internal fire compartmentation functions. Manufactured with 75 mm deep galvanized steel scroll lath curtain, galvanized steel ‘L’ shaped bottom rail and channel profiled vertical side guides. The main head assembly comprises of mild steel primed end plates and angle fixing brackets, tubular rotating barrel assembly complete with a three sided chamfered hood casing formed from 20 swg galvanized sheet steel. Weight of whole door assembly (static load): 30 kgs/m². Performance:Environmental ingress protection level (motor & controls): No performance determined - use in dry, dust free environments only.Motor Drive duty rating: Class S3, 30 %.Fire resistance in accordance with BS 476-22: 1 hour.Fire performance to DIN 4102: Door section element materials Class A2 (non-flammable). CE Marked with manufacturer's declaration of conformity.Arrangement: Face fixed vertical roller shutter.Shutter curtain: Solid, 75 mm concaved, single skinned, galvanized, cold rolled steel.Operation: Power operation of the door is provided by a 230 v1ph tubular motor, which is discreetly fitted within the door roller-barrel. The system also comprises a control panel combining an un-interruptible power supply and the operation interface for normal and fire operation. The product is specifically designed for low cycle usage and is generally intended to be normally left in the open position for automatic activation in the event of a fire alarm signal, or closed on a daily basis for loss prevention/ security purposes. Fire Activation Systems: On receipt of the fire signal, the control panel will send a signal to close the door under power. During Fire operation the key switch or rocker switch are isolated to ensure closure of the door cannot be inhibited. Central to the operation is the fact that power for the system is maintained even in the event of mains failure. System power is ensured by the integral back up power circuit that incorporates sealed batteries and a trickle charger. Should mains power fail during fire operation there is sufficient system power to close the door. The control panel is provided with diagnostic LEDs mounted on the front of the enclosure. These indicate 'Mains operation', 'Battery operation' and 'Fault', for example if the battery power is low. Finish as delivered: Self-coloured – hot dipped zinc coated steel, type G275 coating, grade Z2 bending & profiling quality.Dimensions: Any door size can be accommodated up to a maximum of 5 m².Finish Optional polyester powder coat finish can be supplied to the whole or part of the door assemblies.Colour (for polyester powder coated finish): Many RAL or BS 4800 none metallic ranges are available as standard - other colours can be provided.Operation: A comprehensive range of fire activation systems with auxillary audible/ visual and safety devices are available to accommodate a range of fire strategies.Normal (standard) The door can be opened and closed for security purposes using a key switch or rocker switch. - System Requirements:A suitable fire signal.A 230v 1ph 6amp fused spur for mains power.- Fire:The control panel is designed to accept any of the following fire signals:Normally open, volt free 'clean' contact, which closes on alarm. Normally closed, volt free 'clean' contact, which opens on alarm. 24 v DC supply that is provided in alarm condition. 24 v DC supply that is interrupted in alarm condition. Ironmongery: It is not normal practice to supply secondary locking devices on life safety equipment. However secondary, key operated lath locks can be supplied, if particularly required for additional security.Product literature:http://www.ribaproductselector.com/documentdetails.aspx?ci=03743&f=COL264135.pdf&pg=5

A power operated steel single-skinned fire resistant automatic vertical shutter consisting of concave, solid profiles. Offers good security and fire resistance with a lighter duty material construction than the larger Firetex 240 model and the additional benefit of a concealed electric motor drive system Fire performance to DIN 4102: Door section element materials are Class A2 (non-flammable) and have been tested and assessed to provide maximum 1 hour resistance in accordance with BS 476-22.

Gilgen commercial duty, electrically operated steel fire resistant vertical rolling shutter doors are designed for small apertures in industrial and commercial applications and are suitable for automatic internal fire compartmentation functions. Manufactured with 75 mm deep galvanized steel scroll lath curtain, galvanized steel ‘L’ shaped bottom rail and channel profiled vertical side guides. The main head assembly comprises of mild steel primed end plates and angle fixing brackets, tubular rotating barrel assembly complete with a three sided chamfered hood casing formed from 20 swg galvanized sheet steel.

More about Firetex 60 Tubular Motor:
As standard - Options

Firetex 60 Tubular Motor
 Manufacturer:
Gilgen Door Systems UK Ltd.
  -Web:www.gilgendoorsystems.co.uk.
  -Tel:+44 (0)800 316 6994.
  -Product reference:
Firetex 60 Tubular Motor.
 Size:
[ ______ ] - Insert dimensions or refer to schedule.
 Arrangement:
[Face fixed].
 Finish/ Colour:
[Manufacturer's standard].
[Polyester powder coat, BS 4800]. - Insert colour reference.
[Polyester powder coat, RAL]. - Insert RAL colour reference.
 Operation/ Fire activation:
[Manufacturers standard].
[a - Local heat detection].
 Frame/ Guides:
[2.6 mm thick galvanized steel side guides].
[4 > 6 mm thick, mild steel BZP steel end plate anchor brackets].
 Accessories:
[Not required].
[Removable motor cover]. - Optional to the standard head casing cover.
[Secondary, key operated lath locks].


top ^

Guidance

for Firetex 60 Tubular Motor

from Gilgen Door Systems UK Ltd

More about Firetex 60 Tubular Motor: As standard - Options

As standard

Weight of whole door assembly (static load):

30 kgs/m².

Performance:

  • Environmental ingress protection level (motor & controls): No performance determined - use in dry, dust free environments only.
  • Motor Drive duty rating: Class S3, 30 %.
  • Fire resistance in accordance with BS 476-22: 1 hour.
  • Fire performance to DIN 4102: Door section element materials Class A2 (non-flammable). CE Marked with manufacturer's declaration of conformity.

Arrangement:

Face fixed vertical roller shutter.

Shutter curtain:

Solid, 75 mm concaved, single skinned, galvanized, cold rolled steel.

Operation:

Power operation of the door is provided by a 230 v1ph tubular motor, which is discreetly fitted within the door roller-barrel. The system also comprises a control panel combining an un-interruptible power supply and the operation interface for normal and fire operation. The product is specifically designed for low cycle usage and is generally intended to be normally left in the open position for automatic activation in the event of a fire alarm signal, or closed on a daily basis for loss prevention/ security purposes.

Fire Activation Systems:

On receipt of the fire signal, the control panel will send a signal to close the door under power. During Fire operation the key switch or rocker switch are isolated to ensure closure of the door cannot be inhibited. Central to the operation is the fact that power for the system is maintained even in the event of mains failure. System power is ensured by the integral back up power circuit that incorporates sealed batteries and a trickle charger. Should mains power fail during fire operation there is sufficient system power to close the door. The control panel is provided with diagnostic LEDs mounted on the front of the enclosure. These indicate 'Mains operation', 'Battery operation' and 'Fault', for example if the battery power is low.

Finish as delivered:

Self-coloured – hot dipped zinc coated steel, type G275 coating, grade Z2 bending & profiling quality.

Options

Dimensions:

Any door size can be accommodated up to a maximum of 5 m².

Finish Optional polyester powder coat finish can be supplied to the whole or part of the door assemblies.

Colour (for polyester powder coated finish):

Many RAL or BS 4800 none metallic ranges are available as standard - other colours can be provided.

Operation:

A comprehensive range of fire activation systems with auxillary audible/ visual and safety devices are available to accommodate a range of fire strategies.

Normal (standard)

The door can be opened and closed for security purposes using a key switch or rocker switch.

- System Requirements:

  • A suitable fire signal.
  • A 230v 1ph 6amp fused spur for mains power.

- Fire:

The control panel is designed to accept any of the following fire signals:

  • Normally open, volt free 'clean' contact, which closes on alarm.
  • Normally closed, volt free 'clean' contact, which opens on alarm.
  • 24 v DC supply that is provided in alarm condition.
  • 24 v DC supply that is interrupted in alarm condition.

Ironmongery:

It is not normal practice to supply secondary locking devices on life safety equipment. However secondary, key operated lath locks can be supplied, if particularly required for additional security.

Further Information

Literature:


RIBA CPD

CPD information is available for Gilgen Door Systems UK Ltd from ribacpd.com.

RIBA Product Selector

Additional information may be available for Gilgen Door Systems UK Ltd from ribaproductselector.com.

Contacts:

www.gilgendoorsystems.co.uk

info@gilgendoorsystems.co.uk

T: +44 (0)800 316 6994

F: +44 (0)800 316 6995

Drag work item to add to schedule

top ^

 
NBS Plus
NBS Building, online library, 16 December 2017