A-Z Manufacturers (Coopers Fire Ltd) |  CAWS Index

View larger image of FireMaster® Concertina™ - Closed from Coopers Fire LtdFireMaster® Concertina™ - Closed

Active fire curtain barrier assembly comprising technologically advanced fire-resistant fabric barriers encased in a compact steel housing, available in closed shapes, such as squares and faceted circles. Barriers remain invisibly retracted until activated by an alarm or detector signal, at which time they descend safely to their fire operational position.To be compliant, fire barriers must be protected from a short circuit and or total power failure, this is achieved with the patented Total Gravity Fail-Safe (TGFS) system. Fire barriers will control the spread of fire in a building.Applications include atria, escalators and stairs, and will remain hidden within the ceiling until deployed.Operation:The barrier assemblies commence movement upon initiation or any initiation, power or system failure and move to the fire operational position with site specific adjustable and synchronized velocities within the range of 0.06–0.15 m/s using the unique VarioSpeed™ function. In the event of mains power failure, they remain retracted using their own dedicated battery back-up power supply for a pre-determined period (nominally 30 minutes). If signalled to descend during this period, they fail-safe by gravity in a controlled manner to their fire operational position. At the end of the pre-determined time delay they fail-safe by gravity in a controlled manner. This safety feature is essential to avoid dangerous guillotine/ free-fall deployment.Fabric:Fabric type is EFP™ 4/1000, a glass fibre, stainless steel wire reinforced, fabric coated with a micronized aluminium filled fire retardant polyurethane, nominal 690 g/m². It is in compliance with the requirements of Class 0 to meet the statutory guidance in Building Regulations (E&W) Approved Document B (Volumes 1 and 2).Standards:Compliant to PAS 121:2007 (where applicable).Warranty:One year.Fire resistance:240 minutes (four hours) integrity.Radiation resistance:120 minutes <15 kW/m². Power supply:230 V AC 50 Hz dedicated supply via 12 A un-switched fused spur. Backup battery: Two 12 V 12A/h lead acid batteries.Alarm signal:Normally closed volt-free contacts, open on activation.Display:Power on, alarm active and alarm off.Power supply size (w x h x d):400 x 500 x 210 mm.Motor control unit size (w x h x d):300 x 200 x 80 mm.Size (maximum):Available in unlimited widths and drops up to 8.0 m.Side channels:Side channels seal the curtain fabric and the building. Fire can cause extreme positive or negative pressures (up to 20 Pa). Side guide channels are constructed from galvanized steel (available in standard RAL colours) that can be either surface mounted or recessed into the wall structure to give a flush finish.Concealment:A range of ceiling interfaces are available and can even invisibly conceal the barriers in the ceiling whilst still allowing access for service and maintenance. All systems remain totally concealed when non-operational.Fixing:Fixing options to suit all types of ceiling configuration are available (can be integrated with both solid and suspended ceilings and will remain hidden within the ceiling until deployed).

Active fire curtain barrier assembly comprising technologically advanced fire-resistant fabric barriers encased in a compact steel housing, available in closed shapes, such as squares and faceted circles. Barriers remain invisibly retracted until activated by an alarm or detector signal, at which time they descend safely to their fire operational position.

To be compliant, fire barriers must be protected from a short circuit and or total power failure, this is achieved with the patented Total Gravity Fail-Safe (TGFS) system. Fire barriers will control the spread of fire in a building.

Applications include atria, escalators and stairs, and will remain hidden within the ceiling until deployed.

Operation:

The barrier assemblies commence movement upon initiation or any initiation, power or system failure and move to the fire operational position with site specific adjustable and synchronized velocities within the range of 0.06–0.15 m/s using the unique VarioSpeed™ function.

In the event of mains power failure, they remain retracted using their own dedicated battery back-up power supply for a pre-determined period (nominally 30 minutes). If signalled to descend during this period, they fail-safe by gravity in a controlled manner to their fire operational position. At the end of the pre-determined time delay they fail-safe by gravity in a controlled manner. This safety feature is essential to avoid dangerous guillotine/ free-fall deployment.

Fabric:

Fabric type is EFP™ 4/1000, a glass fibre, stainless steel wire reinforced, fabric coated with a micronized aluminium filled fire retardant polyurethane, nominal 690 g/m². It is in compliance with the requirements of Class 0 to meet the statutory guidance in Building Regulations (E&W) Approved Document B (Volumes 1 and 2).

Standards:

Compliant to PAS 121:2007 (where applicable).

Warranty:

One year.

More about FireMaster® Concertina™ - Closed:
As standard - Options

FireMaster® Concertina™ - Closed
 Manufacturer:
Coopers Fire Ltd.
  -Web:www.coopersfire.com.
  -Tel:+44 (0)23 9245 4405.
  -Product reference:
FireMaster® Concertina™ - Closed.
 Size/Shape:
[ ______ ] - Insert requirements.
 Concealment:
[Flush fit].
[Suspended ceiling with recessed shallow gap].
[Suspended ceiling with patented SLAT™]. - Self levelling access trim.
 Fixing:
[I beam].
[Soffit].
[Suspended with unistrut fit].
  -Accessories:
[None].
[Split drop delay]. - To partially deploy to pre-determined level to permit escape, and initial smoke containment. After delay fully deploys to its fire operational position when mains, or emergency power is available.
[Visual alert system]. - Light warning system when mains or emergency power is available.
[Voice warning]. - Audio or spoken multi message facility when mains or emergency power is available.


top ^

Guidance

for FireMaster® Concertina™ - Closed

from Coopers Fire Ltd

More about FireMaster® Concertina™ - Closed: As standard - Options

As standard

Fire resistance:

240 minutes (four hours) integrity.

Radiation resistance:

120 minutes <15 kW/m².

Power supply:

230 V AC 50 Hz dedicated supply via 12 A un-switched fused spur. Backup battery: Two 12 V 12A/h lead acid batteries.

Alarm signal:

Normally closed volt-free contacts, open on activation.

Display:

Power on, alarm active and alarm off.

Power supply size (w x h x d):

400 x 500 x 210 mm.

Motor control unit size (w x h x d):

300 x 200 x 80 mm.

Options

Size (maximum):

Available in unlimited widths and drops up to 8.0 m.

Side channels:

Side channels seal the curtain fabric and the building. Fire can cause extreme positive or negative pressures (up to 20 Pa). Side guide channels are constructed from galvanized steel (available in standard RAL colours) that can be either surface mounted or recessed into the wall structure to give a flush finish.

Concealment:

A range of ceiling interfaces are available and can even invisibly conceal the barriers in the ceiling whilst still allowing access for service and maintenance. All systems remain totally concealed when non-operational.

Fixing:

Fixing options to suit all types of ceiling configuration are available (can be integrated with both solid and suspended ceilings and will remain hidden within the ceiling until deployed).

Further Information

Literature:

RIBA CPD

CPD information is available for Coopers Fire Ltd from ribacpd.com.

RIBA Product Selector

Additional information may be available for Coopers Fire Ltd from ribaproductselector.com.

Contacts:

www.coopersfire.com

info@coopersfire.com

T: +44 (0)23 9245 4405

F: +44 (0)23 9249 2732

Drag work item to add to schedule