View larger image of Escalator Fire Resistant Roller Shutters from Bolton Gate Co LtdEscalator Fire Resistant Roller Shutters

An electrically operated horizontal shutter designed to provide fire compartmentation between floors of shops, or stores where escalators, travelators or stairwells are present. Available in various configurations, the design parameters are versatile allowing the shutter to be incorporated within light wells or plant rooms as special tank covers. Variable escalator rake angles can be accommodated and fully horizontal arrangements are available. Each unit is factory tested and pre-assembled. Curtain:Constructed from curved section galvanized steel laths with malleable iron endlocks. The laths are connected at each end to the heavy duty drive chain ensuring smooth running in the side guides. A bottom rail is fitted to provide complete closure.Shutter box:Constructed from mild steel endplates fitted with bearing wheels for roller and gears with securing angles for bolting to the floor. The sides of the box are clad with steel sheets to complete the fire resisting assembly. The roller barrel is mounted on a central shaft which is retained in bearings and incorporates a patented constant tension spring mechanism to ensure even coiling.Side guides:Fabricated from mild steel plates designed for fitting to supporting balustrades or concrete block side walls. A section of the guide top plate is removable for maintenance purposes. Speed of operation: Approximately 10 m/minute.Fire resistance:Conforms to BS 476 - up to 4 hours fire resistance. L.P.C.B. Certified.Additional requirements:Audio/ visual panels.Balustrades for side guide support.Brush strips to the side guides.Fire resisting cladding for balustrades.Quartzoid bulb/ micro switch to activate the shutter.Smoke/ Heat detectors.Product literature:http://www.ribaproductselector.com/documentdetails.aspx?ci=00979&f=COL505462.pdf&pg=0LPC approved

An electrically operated horizontal shutter designed to provide fire compartmentation between floors of shops, or stores where escalators, travelators or stairwells are present. Available in various configurations, the design parameters are versatile allowing the shutter to be incorporated within light wells or plant rooms as special tank covers. Variable escalator rake angles can be accommodated and fully horizontal arrangements are available. Each unit is factory tested and pre-assembled.

Curtain:

Constructed from curved section galvanized steel laths with malleable iron endlocks. The laths are connected at each end to the heavy duty drive chain ensuring smooth running in the side guides. A bottom rail is fitted to provide complete closure.

Shutter box:

Constructed from mild steel endplates fitted with bearing wheels for roller and gears with securing angles for bolting to the floor. The sides of the box are clad with steel sheets to complete the fire resisting assembly. The roller barrel is mounted on a central shaft which is retained in bearings and incorporates a patented constant tension spring mechanism to ensure even coiling.

Side guides:

Fabricated from mild steel plates designed for fitting to supporting balustrades or concrete block side walls. A section of the guide top plate is removable for maintenance purposes.

More about Escalator Fire Resistant Roller Shutters:
As standard - Options - Approvals

Escalator Fire Resistant Roller Shutters
 Manufacturer:
Bolton Gate Co Ltd.
  -Web:www.boltongate.co.uk.
  -Tel:+44 (0)1204 871001.
  -Product reference:
Escalator Fire Resistant Roller Shutters.
 Size:
15 x 5 m.
 Operation:
[24V DC motor from battery supply with 240v single-phase, 50 Hz mains supply].
[415V AC, 3 phase, 50 Hz motor].
 Finish:
[Polyester powder coated].
[Standard galvanized shutter curtains and guide. Prime painted to non-galvanized components].


top ^

Guidance

for Escalator Fire Resistant Roller Shutters

from Bolton Gate Co Ltd

More about Escalator Fire Resistant Roller Shutters: As standard - Options - Approvals

As standard

Speed of operation:

Approximately 10 m/minute.

Fire resistance:

Conforms to BS 476 - up to 4 hours fire resistance. L.P.C.B. Certified.

Options

Additional requirements:

  • Audio/ visual panels.
  • Balustrades for side guide support.
  • Brush strips to the side guides.Fire resisting cladding for balustrades.
  • Quartzoid bulb/ micro switch to activate the shutter.
  • Smoke/ Heat detectors.

Approvals

  • LPC approved .

Further Information

Literature:


RIBA Product Selector

Additional information may be available for Bolton Gate Co Ltd from ribaproductselector.com.

Contacts:

www.boltongate.co.uk

sales@boltongate.co.uk

T: +44 (0)1204 871001

F: +44 (0)1204 871049

Drag work item to add to schedule

top ^

 
NBS Plus
NBS Building, online library, 12 December 2017