This NBS Plus page covers modular ceiling, ceiling panel, modular partition with removable cladding, modular ceiling with removable cladding and partition

relating to clause 135 RELOCATABLE PARTITION/ CEILING SYSTEM

in K30 Panel partitions.

For more NBS Plus information from this company, see the Dagard SAS overview page which includes a clause list and a product list.


Products from Dagard SAS

Bookmark
PPM80 - Modular ceiling on a steel frame.
Bookmark
PSM60 - Ceiling panel with a metal facing and a mineral wool core.
Bookmark
PST60 - Ceiling panel with a metal facing and an aluminium honeycomb core.
Bookmark
SD90 - Modular partition SD with removable cladding.
Bookmark
SD100 - Modular ceiling with removable cladding.
Bookmark
SM60 - Partition with a metal facing and mineral wool core.
Bookmark
ST60 - Partition with a metal facing and an aluminium honeycomb core.
 

View larger image of PPM80 from Dagard SASPPM80

A bespoke modular ceiling, composed of a frame positioned according to a regular grid with various sized infill panels which are easily interchangeable.The modular ceiling consists of a lacquered steel frame and infill panels.Various panels are available including different thicknesses (60 or 80 mm), different materials such as mineral wool or aluminium honeycomb core, and different cladding options.Panels can be cut for the inclusion of terminal parts for air treatment, light fittings, etc.Modules are available with a maximum panel width of 1200 mm. The product offers flexibility to fit all configurations and projects.Uniform load allowed for deflection (1/400th length):Panels of thickness 60 mm with mineral wool or aluminium honeycomb core: > 150 daN/m².Panels of thickness 80 mm with mineral wool core: > 150 daN/m².Panels of thickness 80 mm with aluminium honeycomb core: > 250 daN/m².Technical characteristics:Thermal insulation: Dependent on the core and thickness used.Fire reaction: Euroclass A2-s1,d0 and Class 0.

A bespoke modular ceiling, composed of a frame positioned according to a regular grid with various sized infill panels which are easily interchangeable.

The modular ceiling consists of a lacquered steel frame and infill panels.

Various panels are available including different thicknesses (60 or 80 mm), different materials such as mineral wool or aluminium honeycomb core, and different cladding options.

Panels can be cut for the inclusion of terminal parts for air treatment, light fittings, etc.

Modules are available with a maximum panel width of 1200 mm. The product offers flexibility to fit all configurations and projects.

More about PPM80:
As standard - Further information.

PendingMODULAR CEILING:
 Manufacturer:
Dagard SAS.
  -Web:www.dagard.com/gb/.
  -Tel:+33 (0)555 824000.
  -Product reference:
PPM80.
 Panel:
  -Width:
[ ______ ] - 1200 mm (maximum). Consult manufacturer and insert requirements.
  -Length:
[ ______ ] - Consult manufacturer and insert requirements.
  -Thickness:
[60 mm].
[80 mm].
  -Core material:
[Aluminium honeycomb].
[Mineral wool].
 Cladding:
  -Type:
[ ______ ] - Consult manufacturer and insert requirements.
  -Colour/ Finish:
[ ______ ] - Consult manufacturer and insert requirements.
 Accessories:
[None].
[Air terminals].
[Light fittings].


top ^

Guidance

for PPM80

from Dagard SAS

More about PPM80: As standard - Further information.

As standard

Uniform load allowed for deflection (1/400th length):

  • Panels of thickness 60 mm with mineral wool or aluminium honeycomb core: > 150 daN/m².
  • Panels of thickness 80 mm with mineral wool core: > 150 daN/m².
  • Panels of thickness 80 mm with aluminium honeycomb core: > 250 daN/m².

Technical characteristics:

  • Thermal insulation: Dependent on the core and thickness used.
  • Fire reaction: Euroclass A2-s1,d0 and Class 0.

Further Information

Literature:

RIBA Product Selector

Additional information may be available for Dagard SAS from ribaproductselector.com.

Contacts:

www.dagard.com/gb/

T: +33 (0)555 824000

top ^

 

View larger image of PSM60 from Dagard SASPSM60

The ceiling is designed for rooms which must be kept completely free of microbiological contamination.The non-combustible modular panels are 60 mm thick and manufactured from time-stable materials and no emitting particles.The ceiling provides smooth surfaces which are easy to clean, are air-tight and offer good insulation.Components:Core: Hydrophobic rock wool plates. Density: 100 kg/m³. Fire reaction according to EN 13501-1: A1.Adhesive: Bi-component polyurethane.Silicone sealant (quality-label SNJF; complies with FDA 21 CFR 175.105).Polymer MS caulk.Flexible sealant in closed cell reticulate polyethene adhesive strips (over the ceiling), density 50 kg/m³.The system uses an aluminium key profile that is integrated into the grooves of the four sides of the ceiling panel. A metallic profile is integrated into the grooves in order to hang the ceiling panels to the building structure.On request, the two facings can be manufactured from different materials on the inside and outside faces (aspect, colour and/ or thickness).Panel:- Thickness:60 mm.- Profile:Metallic profile for passage of cables.Acceptable span in ceiling:Without opening: 2.4 m (walkable), 3.2 m (non-walkable).With opening: 1.6–2.4 m (walkable), 2.4–3.2 m (non-walkable), depending on configuration. Consult literature for details.Loads taken into account for measurement: 60 daN/m² (panel weight included, panel on two supports) plus 150 daN (if accessible ceiling, concentrated load at any point of the ceiling).Small sections can be cut out (width: <600 mm) without compromising the safety of the ceiling.With non-standard openings (width: >0.665 m and/ or area: >0.45 m²) it is necessary to use additional fastening joist.The ceiling is not a technical platform; for maintenance, it will support the passage of one person.Technical characteristics:Thermal conductivity coefficient lambda: 0.041 W/mK.Thermal transmission coefficient Uc: 0.612 W/mK.R-value: 1.6.Acceptable resisting to buckling: ≥210 kPa (2.1 daN/cm²).Weight 17 kg/m² (two faces, 0.6 mm thick).Fire reaction: Euroclass A2-s1,d0 and Class 0.Flame spread index (ASTM E84-01): Class 1.Flame spread (BS 476-7): Class 1.Fire spread index (BS 476-6): 0.7.0FM approval (standard 4880)Class 10UL approval (cable routing)Safety E471046

The ceiling is designed for rooms which must be kept completely free of microbiological contamination.

The non-combustible modular panels are 60 mm thick and manufactured from time-stable materials and no emitting particles.

The ceiling provides smooth surfaces which are easy to clean, are air-tight and offer good insulation.

Components:

  • Core: Hydrophobic rock wool plates. Density: 100 kg/m³. Fire reaction according to EN 13501-1: A1.
  • Adhesive: Bi-component polyurethane.
  • Silicone sealant (quality-label SNJF; complies with FDA 21 CFR 175.105).
  • Polymer MS caulk.
  • Flexible sealant in closed cell reticulate polyethene adhesive strips (over the ceiling), density 50 kg/m³.

The system uses an aluminium key profile that is integrated into the grooves of the four sides of the ceiling panel. A metallic profile is integrated into the grooves in order to hang the ceiling panels to the building structure.

On request, the two facings can be manufactured from different materials on the inside and outside faces (aspect, colour and/ or thickness).

More about PSM60:
As standard - Approvals - Further information.

PendingCEILING PANEL:
 Manufacturer:
Dagard SAS.
  -Web:www.dagard.com/gb/.
  -Tel:+33 (0)555 824000.
  -Product reference:
PSM60.
 Panel:
  -Width:
[350 mm].
[550 mm].
[1200 mm]. - 6000 mm maximum length only.
  -Length:
[4000 mm].
[6000 mm].
 Facing:
  -Thickness:
[0.5 mm]. - Polyester 25 μm lacquer finish only.
[0.6 mm]. - Standard.
[0.8 mm]. - Polyester 25 μm lacquer and stainless steel polished S4 finishes only.
  -Material:
[Smooth stainless steel sheet, 1.4307 (304 L) grade].
[Smooth stainless steel sheet, 1.4404 (316 L) grade].
[Steel sheet S280 GD, hot-dip galvanized Z225]. - 225 g/m² of zinc on the two faces or similar.
  -Coating:
[Polished S4]. - Stainless steel only.
[Polyester 25 µm lacquer]. - Class in accordance with XP P 34-301: lIIa.
[Polyester lacquer and PET film of total thickness 55 µm]. - Class in accordance with XP P 34-301: Vc.
 Colour/ Finish:
Iceberg white (similar to RAL 9010).


top ^

Guidance

for PSM60

from Dagard SAS

More about PSM60: As standard - Approvals - Further information.

As standard

Panel:

- Thickness:

60 mm.

- Profile:

Metallic profile for passage of cables.

Acceptable span in ceiling:

  • Without opening: 2.4 m (walkable), 3.2 m (non-walkable).
  • With opening: 1.6–2.4 m (walkable), 2.4–3.2 m (non-walkable), depending on configuration. Consult literature for details.
  • Loads taken into account for measurement: 60 daN/m² (panel weight included, panel on two supports) plus 150 daN (if accessible ceiling, concentrated load at any point of the ceiling).
  • Small sections can be cut out (width: <600 mm) without compromising the safety of the ceiling.
  • With non-standard openings (width: >0.665 m and/ or area: >0.45 m²) it is necessary to use additional fastening joist.
  • The ceiling is not a technical platform; for maintenance, it will support the passage of one person.

Technical characteristics:

  • Thermal conductivity coefficient lambda: 0.041 W/mK.
  • Thermal transmission coefficient Uc: 0.612 W/mK.
  • R-value: 1.6.
  • Acceptable resisting to buckling: ≥210 kPa (2.1 daN/cm²).
  • Weight 17 kg/m² (two faces, 0.6 mm thick).
  • Fire reaction: Euroclass A2-s1,d0 and Class 0.
  • Flame spread index (ASTM E84-01): Class 1.
  • Flame spread (BS 476-7): Class 1.
  • Fire spread index (BS 476-6): 0.7.

Approvals

  • FM approval (standard 4880): Class 1.
  • UL approval (cable routing): Safety E471046.

Further Information

Literature:

RIBA Product Selector

Additional information may be available for Dagard SAS from ribaproductselector.com.

Contacts:

www.dagard.com/gb/

T: +33 (0)555 824000

top ^

 

View larger image of PST60 from Dagard SASPST60

The ceiling is designed for rooms which must be kept completely free of microbiological contamination.The non-combustible modular panels are 60 mm thick and manufactured from time-stable materials and no emitting particles.The ceiling provides smooth surfaces which are easy to clean, are air-tight and offer good insulation.A metallic profile is integrated into the grooves in order to hang the ceiling panels to the building structure.Components:Core: Aluminium honeycomb, link diameter 19 mm metal strip thickness 70 μ (ceiling panel). Alloy 3003 (EN 573 standard), with a rustproof treatment. Density: 28 kg/m³ (70 μ). Fire reaction: Non-combustible. Resistance to compression: Average value of 270 kPa.Adhesive: Bi-component polyurethane.Silicone sealant (quality-label SNJF; complies with FDA 21 CFR 175.105).Polymer MS caulk.Flexible sealant in closed cell reticulate polyethene adhesive strips (over the ceiling), density of 50 kg/m³.On request, the two facings can be manufactured from different materials on the inside and outside faces (aspect, colour and/ or thickness).Panel:- Thickness:60 mm.- Profile:Metallic profile for passage of cables.Acceptable span in ceiling:Without opening: 3 m (walkable), 5 m (non-walkable).With opening: 2–2.8 m (walkable), 2.4–4 m (non-walkable), depending on configuration. Consult literature for details.Loads taken into account for measurement: 60 daN/m² (panel weight included, panel on two supports) plus 150 daN (if accessible ceiling, concentrated load at any point of the ceiling).Small sections can be cut out (width: <600 mm) without compromising the safety of the ceiling.With nonstandard openings (width: >0.665 m and/ or area: >0.45 m²) it is necessary to use additional fastening joist.The ceiling is not a technical platform; for maintenance, it will support the passage of one person.Permissible loads:Varies depending on span and beam; consult literature for details.Technical characteristics:Weight: 10.7 kg/m² (two faces, 0.5 mm thick steel); 6.9 kg/m² (two faces, 0.67 mm aluminium).Fire reaction: Euroclass A2-s1,d0.0FM approval (standard 4880)Class 10UL approval (cable routing)Safety E471046

The ceiling is designed for rooms which must be kept completely free of microbiological contamination.

The non-combustible modular panels are 60 mm thick and manufactured from time-stable materials and no emitting particles.

The ceiling provides smooth surfaces which are easy to clean, are air-tight and offer good insulation.

A metallic profile is integrated into the grooves in order to hang the ceiling panels to the building structure.

Components:

  • Core: Aluminium honeycomb, link diameter 19 mm metal strip thickness 70 μ (ceiling panel). Alloy 3003 (EN 573 standard), with a rustproof treatment. Density: 28 kg/m³ (70 μ). Fire reaction: Non-combustible. Resistance to compression: Average value of 270 kPa.
  • Adhesive: Bi-component polyurethane.
  • Silicone sealant (quality-label SNJF; complies with FDA 21 CFR 175.105).
  • Polymer MS caulk.
  • Flexible sealant in closed cell reticulate polyethene adhesive strips (over the ceiling), density of 50 kg/m³.

On request, the two facings can be manufactured from different materials on the inside and outside faces (aspect, colour and/ or thickness).

More about PST60:
As standard - Approvals - Further information.

PendingCEILING PANEL:
 Manufacturer:
Dagard SAS.
  -Web:www.dagard.com/gb/.
  -Tel:+33 (0)555 824000.
  -Product reference:
PST60.
 Panel:
  -Width:
[350 mm].
[550 mm].
[1200 mm]. - 6000 mm maximum length only.
  -Length:
[4000 mm].
[6000 mm].
 Facing:
  -Thickness:
[0.5 mm]. - Polyester 25 μm lacquer finish only.
[0.6 mm]. - Standard.
[0.8 mm]. - Polyester 25 μm lacquer and stainless steel polished S4 finishes only.
  -Material:
[Smooth stainless steel sheet, 1.4307 (304 L) grade].
[Smooth stainless steel sheet, 1.4404 (316 L) grade].
[Steel sheet S280 GD, hot-dip galvanized Z225]. - 225 g/m² of zinc on the two faces or similar.
    Coating:
[Polished S4]. - Stainless steel only.
[Polyester 25 µm lacquer]. - Class in accordance with XP P 34-301: lIIa.
[Polyester lacquer and PET film of total thickness 55 µm]. - Class in accordance with XP P 34-301: Vc.
 Colour/ Finish:
Iceberg white (similar to RAL 9010).


top ^

Guidance

for PST60

from Dagard SAS

More about PST60: As standard - Approvals - Further information.

As standard

Panel:

- Thickness:

60 mm.

- Profile:

Metallic profile for passage of cables.

Acceptable span in ceiling:

  • Without opening: 3 m (walkable), 5 m (non-walkable).
  • With opening: 2–2.8 m (walkable), 2.4–4 m (non-walkable), depending on configuration. Consult literature for details.
  • Loads taken into account for measurement: 60 daN/m² (panel weight included, panel on two supports) plus 150 daN (if accessible ceiling, concentrated load at any point of the ceiling).
  • Small sections can be cut out (width: <600 mm) without compromising the safety of the ceiling.
  • With nonstandard openings (width: >0.665 m and/ or area: >0.45 m²) it is necessary to use additional fastening joist.
  • The ceiling is not a technical platform; for maintenance, it will support the passage of one person.

Permissible loads:

Varies depending on span and beam; consult literature for details.

Technical characteristics:

  • Weight: 10.7 kg/m² (two faces, 0.5 mm thick steel); 6.9 kg/m² (two faces, 0.67 mm aluminium).
  • Fire reaction: Euroclass A2-s1,d0.

Approvals

  • FM approval (standard 4880): Class 1.
  • UL approval (cable routing): Safety E471046.

Further Information

Literature:

RIBA Product Selector

Additional information may be available for Dagard SAS from ribaproductselector.com.

Contacts:

www.dagard.com/gb/

T: +33 (0)555 824000

top ^

 

View larger image of SD90 from Dagard SASSD90

Modular partition manufactured from a metallic stud frame and two individually removable skinned panels, allowing the easy incorporation of any services routing, wiring or components.Partition overall thickness: 90 mm (standard), can be increased to suit project requirements.Airtightness is achieved by a bead of mastic (clean room grade silicone caulk, MS Polymer, chemical cold weld) applied on site in the calibrated gaps for all skins.Components:The galvanized steel structural frame consists of:Metallic rails (top and bottom).Proprietary vertical notched metallic studs adjustable in height, placed every 1100 or 1200 mm (optional sub-module).Noggins, cross-members and specific accessories available for incorporation of doors, glazing or specific equipment.Removable cladding:Metallic single or double sided panels.Finished cladding manufactured from thick galvanized steel sheets (0.8 mm), backed with plasterboard/ gypsum wall board (GWB) or aluminium honeycomb core; total thickness 18 mm. Vertically clipped on the studs, with a pre-set gap of 3 mm provided for silicone caulk (gap 0.5 mm for cold welded seal).Doors:Hinged or sliding doors, with one or two leaves available with:A wide range of sizes.Aluminium or lacquered steel door frame (heat-cured epoxy-polyester powder paint, choice of colour).Stainless steel variant set flush on one side or the other, or centred in the partition thickness.Leaves of thickness 60 mm with metallic or high pressure laminate (HPL) facings, choice of colour.Optionally available glazed or flush vision panel, selection of hardware, interlocking management, motorized system and kick plate protection.Glazed modules:Airtight double glass window system with toughened laminated safety glass, double flush.Dimensions on request according to the partition layout.Optional integrated (flush) manual or electrical blinds available.Single size lining partition or two lift panels are optionally available.Module width:1100 mm.

Modular partition manufactured from a metallic stud frame and two individually removable skinned panels, allowing the easy incorporation of any services routing, wiring or components.

Partition overall thickness: 90 mm (standard), can be increased to suit project requirements.

Airtightness is achieved by a bead of mastic (clean room grade silicone caulk, MS Polymer, chemical cold weld) applied on site in the calibrated gaps for all skins.

Components:

The galvanized steel structural frame consists of:

  • Metallic rails (top and bottom).
  • Proprietary vertical notched metallic studs adjustable in height, placed every 1100 or 1200 mm (optional sub-module).
  • Noggins, cross-members and specific accessories available for incorporation of doors, glazing or specific equipment.

Removable cladding:

  • Metallic single or double sided panels.
  • Finished cladding manufactured from thick galvanized steel sheets (0.8 mm), backed with plasterboard/ gypsum wall board (GWB) or aluminium honeycomb core; total thickness 18 mm. Vertically clipped on the studs, with a pre-set gap of 3 mm provided for silicone caulk (gap 0.5 mm for cold welded seal).

Doors:

Hinged or sliding doors, with one or two leaves available with:

  • A wide range of sizes.
  • Aluminium or lacquered steel door frame (heat-cured epoxy-polyester powder paint, choice of colour).
  • Stainless steel variant set flush on one side or the other, or centred in the partition thickness.
  • Leaves of thickness 60 mm with metallic or high pressure laminate (HPL) facings, choice of colour.
  • Optionally available glazed or flush vision panel, selection of hardware, interlocking management, motorized system and kick plate protection.

Glazed modules:

  • Airtight double glass window system with toughened laminated safety glass, double flush.
  • Dimensions on request according to the partition layout.
  • Optional integrated (flush) manual or electrical blinds available.

Single size lining partition or two lift panels are optionally available.

More about SD90:
As standard - Further information.

PendingMODULAR PARTITION WITH REMOVABLE CLADDING:
 Manufacturer:
Dagard SAS.
  -Web:www.dagard.com/gb/.
  -Tel:+33 (0)555 824000.
  -Product reference:
SD90.
 Height:
[ ______ ] - 3000 mm (maximum). Stackable if required. Consult manufacturer and insert requirements.
 Cladding:
  -Type:
[Double sided].
[Single sided].
  -Material/ Finish:
[Galvanized steel 8/10th plus PET 55 µm, iceberg white colour (similar to RAL 9010)].
[Stainless steel sheet 8/10th].
[Stainless steel sheet 8/10th plus antibacterial PVC film 150 µm].
 Doors:
  -Type:
[Hinged].
[Sliding].
  -Leaf:
[One].
[Two].
  -Material:
[ ______ ] - Consult manufacturer and insert requirements.
  -Colour/ Finish:
[ ______ ] - Consult manufacturer and insert requirements.
  -Vision panel:
[Not required].
[Flush].
[Glazed].
  -Accessories:
[Not required].
[Hardware].
[Interlocking management].
 Glazing:
  -Size:
[ ______ ] - Consult manufacturer and insert requirements.
  -Blinds:
[Not required].
[Electric].
[Manual].
 Accessories/ Other requirements:
[None].
[Cross-members].
[Noggins].


top ^

Guidance

for SD90

from Dagard SAS

More about SD90: As standard - Further information.

As standard

Module width:

1100 mm.

Further Information

Literature:

RIBA Product Selector

Additional information may be available for Dagard SAS from ribaproductselector.com.

Contacts:

www.dagard.com/gb/

T: +33 (0)555 824000

top ^

 

View larger image of SD100 from Dagard SASSD100

A walkable modular ceiling, 100 mm thick, which consists of metallic structure profiles and removable cladding (cassettes), allowing initial or future incorporation of cables or other equipment such as light fittings or heating, ventilation and air conditioning (HVAC) terminals.Structural bearers are manufactured from lacquered steel sheet, with a 100 x 60 mm section and a modular span of 1100 or 1200 mm. They are regularly pre-punched on the edge for perpendicular cable routing. Brackets for suspension by M10 rods are integrated every 2400/ 1100 or 1200 mm. Permitted load uniformly distributed UDL: 2.5 KN/m².Lower cladding:The lower cladding is manufactured from lacquered steel, 0.8 mm thick and clamped on the structural bearers.Modular width: 600 or 900 mm.Span: 1200 mm.Cassette size: 600 x 1100 mm or 900 x 1100 mm.System totally flush on under part of the bearers.Pre-cutting for component incorporation is prefabricated off -site.Various finishes available including:Polyester lacquer 25 microns, iceberg white colour (similar to RAL 9010).PET complex 55 microns, iceberg white colour (similar to RAL 9010).Upper cladding:Galvanized steel, 2 mm thick, secured on the structural bearers, independently removable.Modular width: 600 or 900 mm.Span: 1200 mm.Cassette size: 600 x 1100 mm or 900 x 1100 mm.Pre-cutting for incorporation is prefabricated off site.Air-tightness:Airtightness by mastic (silicone caulk, MS Polymer, etc.).Upper joint cover totally flush.Light fitting modules:A set of flush light fittings with lamps or LED totally integrated into a ceiling cassette. The fitting is accessible from the rear part of the ceiling for maintenance purposes. A wide choice of lighting components and designs plus safety options are available. Consult manufacturer for details.HVAC terminal modules:Specific ceiling modules are available for the integration of totally flush HVAC equipment such as air entrance or extraction terminals with or without filters. Consult manufacturer for details.

A walkable modular ceiling, 100 mm thick, which consists of metallic structure profiles and removable cladding (cassettes), allowing initial or future incorporation of cables or other equipment such as light fittings or heating, ventilation and air conditioning (HVAC) terminals.

Structural bearers are manufactured from lacquered steel sheet, with a 100 x 60 mm section and a modular span of 1100 or 1200 mm. They are regularly pre-punched on the edge for perpendicular cable routing. Brackets for suspension by M10 rods are integrated every 2400/ 1100 or 1200 mm. Permitted load uniformly distributed UDL: 2.5 KN/m².

Lower cladding:

  • The lower cladding is manufactured from lacquered steel, 0.8 mm thick and clamped on the structural bearers.
  • Modular width: 600 or 900 mm.
  • Span: 1200 mm.
  • Cassette size: 600 x 1100 mm or 900 x 1100 mm.
  • System totally flush on under part of the bearers.
  • Pre-cutting for component incorporation is prefabricated off -site.

Various finishes available including:

  • Polyester lacquer 25 microns, iceberg white colour (similar to RAL 9010).
  • PET complex 55 microns, iceberg white colour (similar to RAL 9010).

Upper cladding:

  • Galvanized steel, 2 mm thick, secured on the structural bearers, independently removable.
  • Modular width: 600 or 900 mm.
  • Span: 1200 mm.
  • Cassette size: 600 x 1100 mm or 900 x 1100 mm.
  • Pre-cutting for incorporation is prefabricated off site.

Air-tightness:

  • Airtightness by mastic (silicone caulk, MS Polymer, etc.).
  • Upper joint cover totally flush.

Light fitting modules:

A set of flush light fittings with lamps or LED totally integrated into a ceiling cassette. The fitting is accessible from the rear part of the ceiling for maintenance purposes. A wide choice of lighting components and designs plus safety options are available. Consult manufacturer for details.

HVAC terminal modules:

Specific ceiling modules are available for the integration of totally flush HVAC equipment such as air entrance or extraction terminals with or without filters. Consult manufacturer for details.

More about SD100:
- Further information.

PendingMODULAR CEILING WITH REMOVABLE CLADDING:
 Manufacturer:
Dagard SAS.
  -Web:www.dagard.com/gb/.
  -Tel:+33 (0)555 824000.
  -Product reference:
SD100.
 Cassette size:
[600 x 1100 mm].
[900 x 1100 mm].
 Finish:
[ ______ ]
 Accessories/ Other requirements:
[None].
[Grid ceiling frame work with crossed noggins].
[HVAC terminal].


top ^

Guidance

for SD100

from Dagard SAS

Further Information

Literature:

RIBA Product Selector

Additional information may be available for Dagard SAS from ribaproductselector.com.

Contacts:

www.dagard.com/gb/

T: +33 (0)555 824000

top ^

 

View larger image of SM60 from Dagard SASSM60

The SM60 partition is designed for ultra-clean rooms which must be kept completely free of microbiological contamination.The partition consists of non-combustible modular panels, 60 mm thick, manufactured from time-stable materials and no emitting particles.The partition provides smooth surfaces which are easy to clean, are airtight and offer good insulation.Components:Core: Hydrophobic rock wool plates. Density: 80 kg/m³. Fire class according to EN 13501-1: A1.Adhesive: Bi-component polyurethane.Silicone sealant (quality-label SNJF; complies with FDA 21 CFR 175.105).Polymer MS caulk.Profiles integrated into the thickness of SM panels allow the assembly of panels and the passage of cables. The system uses an aluminium key profile that is inserted into the full-length grooves on both sides of the wall panels. A special feature without the link profile allows the partition to become removable panel by panel, due to stainless steel clips.On request, the two facings can be manufactured from different materials on the inside and outside faces (aspect, colour and/ or thickness).Vertical panel thickness:60 mm.Panel profile:Metallic profile for passage of cables.Maximum acceptable loads:Bending resistance, panels on two supports:2.5 m high: 75 q (daN/m²).3 m high: 55 q (daN/m²).3.5 m high: 42 q (daN/m²).4 m high: 30 q (daN/m²).≥ 4.5 m high: 20 q (daN/m²).Technical characteristics:Thermal conductivity coefficient lambda: 0.041 W/mK.Thermal transmission coefficient Uc: 0.612 W/mK.R-value: 1.6.Acceptable resisting to buckling: ≥210 kPa (2.1 daN/cm²).Weight 17 kg/m² (two faces, 0.6 mm thick).Tightness in the whole partition with silicone joint: Qs ≤0,0027 m³/h.m² under ΔP: 50 Pa.Fire reaction: Euroclass A2-s1,d0 and Class 0.Flame spread index (ASTM E84-01): Class 1.Flame spread (BS 476-7): Class 1.Fire spread index (BS 476-6): 0.7.0FM approval (standard 4880)Class 10UL approval (cable routing)Safety E471046

The SM60 partition is designed for ultra-clean rooms which must be kept completely free of microbiological contamination.

The partition consists of non-combustible modular panels, 60 mm thick, manufactured from time-stable materials and no emitting particles.

The partition provides smooth surfaces which are easy to clean, are airtight and offer good insulation.

Components:

  • Core: Hydrophobic rock wool plates. Density: 80 kg/m³. Fire class according to EN 13501-1: A1.
  • Adhesive: Bi-component polyurethane.
  • Silicone sealant (quality-label SNJF; complies with FDA 21 CFR 175.105).
  • Polymer MS caulk.

Profiles integrated into the thickness of SM panels allow the assembly of panels and the passage of cables. The system uses an aluminium key profile that is inserted into the full-length grooves on both sides of the wall panels. A special feature without the link profile allows the partition to become removable panel by panel, due to stainless steel clips.

On request, the two facings can be manufactured from different materials on the inside and outside faces (aspect, colour and/ or thickness).

More about SM60:
As standard - Approvals - Further information.

PendingPARTITION:
 Manufacturer:
Dagard SAS.
  -Web:www.dagard.com/gb/.
  -Tel:+33 (0)555 824000.
  -Product reference:
SM60.
 Vertical panel:
  -Width:
[200 mm].
[250 mm].
[350 mm].
  -Length:
[4000 mm].
[6000 mm].
 Facing:
  -Thickness:
[0.5 mm]. - Polyester 25 μm lacquer finish only.
[0.6 mm]. - Standard.
[0.8 mm]. - Polyester 25 μm lacquer and stainless steel polished S4 finishes only.
  -Material:
[Smooth stainless steel sheet, 1.4307 (304 L) grade].
[Smooth stainless steel sheet, 1.4404 (316 L) grade].
[Steel sheet S280 GD, hot-dip galvanized Z225]. - 225 g/m² of zinc on the two faces or similar.
    Coating:
[Polished S4]. - Stainless steel only.
[Polyester 25 µm lacquer]. - Class in accordance with XP P 34-301: lIIa.
[Polyester lacquer and PET film of total thickness 55 µm]. - Class in accordance with XP P 34-301: Vc.
 Coating:
Iceberg white (similar to RAL 9010).


top ^

Guidance

for SM60

from Dagard SAS

More about SM60: As standard - Approvals - Further information.

As standard

Vertical panel thickness:

60 mm.

Panel profile:

Metallic profile for passage of cables.

Maximum acceptable loads:

  • Bending resistance, panels on two supports:
  • 2.5 m high: 75 q (daN/m²).
  • 3 m high: 55 q (daN/m²).
  • 3.5 m high: 42 q (daN/m²).
  • 4 m high: 30 q (daN/m²).
  • ≥ 4.5 m high: 20 q (daN/m²).

Technical characteristics:

  • Thermal conductivity coefficient lambda: 0.041 W/mK.
  • Thermal transmission coefficient Uc: 0.612 W/mK.
  • R-value: 1.6.
  • Acceptable resisting to buckling: ≥210 kPa (2.1 daN/cm²).
  • Weight 17 kg/m² (two faces, 0.6 mm thick).
  • Tightness in the whole partition with silicone joint: Qs ≤0,0027 m³/h.m² under ΔP: 50 Pa.
  • Fire reaction: Euroclass A2-s1,d0 and Class 0.
  • Flame spread index (ASTM E84-01): Class 1.
  • Flame spread (BS 476-7): Class 1.
  • Fire spread index (BS 476-6): 0.7.

Approvals

  • FM approval (standard 4880): Class 1.
  • UL approval (cable routing): Safety E471046.

Further Information

Literature:

RIBA Product Selector

Additional information may be available for Dagard SAS from ribaproductselector.com.

Contacts:

www.dagard.com/gb/

T: +33 (0)555 824000

top ^

 

View larger image of ST60 from Dagard SASST60

The ST60 partition is designed for rooms which must be kept completely free of microbiological contamination.The partition consists of non-combustible modular panels, 60 mm thick, manufactured from time-stable materials and no emitting particles.The partition provides smooth surfaces which are easy to clean, are airtight and offer good insulation.Components:Core: Aluminium honeycomb, link diameter 19 mm, metal strip thickness 50 µm (vertical panels). Alloy 3003 (EN 573 standard), with rustproof treatment. Density: 20 kg/m³ (50 µ). Fire reaction: Non-combustible. Resistance to compression: Average value: 270 kPa.Adhesive: Bi-component polyurethane.Silicone sealant (quality-label SNJF; complies with FDA 21 CFR 175.105).Polymer MS caulk.Profiles integrated into the thickness of ST panels allow the assembly of panels and the passage of cables. The system uses an aluminium key profile that is inserted into the full-length grooves on both sides of the wall panels. A special feature without the link profile allows the partition to become removable panel by panel, due to stainless steel clips.On request, the two facings can be manufactured from different materials on the inside and outside faces (aspect, colour and/ or thickness).Panel:- Thickness:60 mm.- Profile:Metallic profile for passage of cables.Maximum acceptable loads:Bending resistance, panels on two supports:2.5 m high: 75 q (daN/m²).3 m high: 55 q (daN/m²).3.5 m high: 42 q (daN/m²).4 m high: 30 q (daN/m²).≤5.80 m high: 20 q (daN/m²).Technical characteristics:Thermal conductivity coefficient lambda: 0.041 W/mK.Thermal transmission coefficient Uc: 0.612 W/mK.R-value: 1.6.Weight 10.7 kg/m² (two faces, 0.5 mm thick steel); 6.9 kg/m² (two faces, 0.67 mm aluminium).Tightness in the whole partition with silicone joint: Qs ≤0.0027 m³/h.m² under ΔP: 50 Pa.Fire reaction: Euroclass A2-s1,d0.0FM approval (standard 4880)Class 10UL approval (cable routing)Safety E471046

The ST60 partition is designed for rooms which must be kept completely free of microbiological contamination.

The partition consists of non-combustible modular panels, 60 mm thick, manufactured from time-stable materials and no emitting particles.

The partition provides smooth surfaces which are easy to clean, are airtight and offer good insulation.

Components:

  • Core: Aluminium honeycomb, link diameter 19 mm, metal strip thickness 50 µm (vertical panels). Alloy 3003 (EN 573 standard), with rustproof treatment. Density: 20 kg/m³ (50 µ). Fire reaction: Non-combustible. Resistance to compression: Average value: 270 kPa.
  • Adhesive: Bi-component polyurethane.
  • Silicone sealant (quality-label SNJF; complies with FDA 21 CFR 175.105).
  • Polymer MS caulk.

Profiles integrated into the thickness of ST panels allow the assembly of panels and the passage of cables. The system uses an aluminium key profile that is inserted into the full-length grooves on both sides of the wall panels. A special feature without the link profile allows the partition to become removable panel by panel, due to stainless steel clips.

On request, the two facings can be manufactured from different materials on the inside and outside faces (aspect, colour and/ or thickness).

More about ST60:
As standard - Approvals - Further information.

PendingPARTITION:
 Manufacturer:
Dagard SAS.
  -Web:www.dagard.com/gb/.
  -Tel:+33 (0)555 824000.
  -Product reference:
ST60.
 Panel:
  -Width:
[200 mm].
[250 mm].
[350 mm].
  -Length:
[4000 mm].
[6000 mm].
 Facing:
  -Thickness:
[0.5 mm]. - Polyester 25 μm lacquer finish only.
[0.6 mm]. - Standard.
[0.8 mm]. - Polyester 25 μm lacquer and stainless steel polished S4 finishes only.
  -Material:
[Smooth stainless steel sheet, 1.4307 (304 L) grade].
[Smooth stainless steel sheet, 1.4404 (316 L) grade].
[Steel sheet S280 GD, hot-dip galvanized Z225]. - 225 g/m² of zinc on the two faces or similar.
    Coating:
[Polished S4]. - Stainless steel only.
[Polyester 25 µm lacquer]. - Class in accordance with XP P 34-301: lIIa.
[Polyester lacquer and PET film of total thickness 55 µm]. - Class in accordance with XP P 34-301: Vc.
 Colour/ Finish:
Iceberg white (similar to RAL 9010).


top ^

Guidance

for ST60

from Dagard SAS

More about ST60: As standard - Approvals - Further information.

As standard

Panel:

- Thickness:

60 mm.

- Profile:

Metallic profile for passage of cables.

Maximum acceptable loads:

Bending resistance, panels on two supports:

  • 2.5 m high: 75 q (daN/m²).
  • 3 m high: 55 q (daN/m²).
  • 3.5 m high: 42 q (daN/m²).
  • 4 m high: 30 q (daN/m²).
  • ≤5.80 m high: 20 q (daN/m²).

Technical characteristics:

  • Thermal conductivity coefficient lambda: 0.041 W/mK.
  • Thermal transmission coefficient Uc: 0.612 W/mK.
  • R-value: 1.6.
  • Weight 10.7 kg/m² (two faces, 0.5 mm thick steel); 6.9 kg/m² (two faces, 0.67 mm aluminium).
  • Tightness in the whole partition with silicone joint: Qs ≤0.0027 m³/h.m² under ΔP: 50 Pa.
  • Fire reaction: Euroclass A2-s1,d0.

Approvals

  • FM approval (standard 4880): Class 1.
  • UL approval (cable routing): Safety E471046.

Further Information

Literature:

RIBA Product Selector

Additional information may be available for Dagard SAS from ribaproductselector.com.

Contacts:

www.dagard.com/gb/

T: +33 (0)555 824000

Drag work item to add to schedule

top ^

 
NBS Plus
NBS Building, online library, 12 December 2017